Guides
Lightning and surge protection for solar systems
Most solar damage from storms comes from surges induced in long cables, not direct strikes. Correct surge protectors and good earthing prevent most of it, at a small cost.
Surge protectors (SPD)
- A DC surge protector on the panel side, rated for the PV string voltage (for example 1,000 V DC), close to the inverter
- An AC surge protector in the distribution board on the inverter output and grid side
- A Type 1 device where the building has an external lightning rod or is fed by overhead lines; otherwise Type 2 is common
- Many inverters include basic surge protection, but external SPDs protect better and are cheap to replace
Earthing and bonding
Bond all panel frames and the mounting structure together and to the main earth with a copper conductor of suitable size. Keep a single earthing system for the building so there are no voltage differences between earths. Have the earth resistance measured; follow your local electrical code for the required values.
Cable routing
Run the positive and negative DC cables side by side to keep the loop area small, use the shortest practical routes, and keep PV cables away from lightning-rod down conductors.
Before the storm season
Check the SPD status windows (most turn red when they need replacing), the earth connections and any burnt marks. Our inverters and mounting systems can be supplied with matching DC and AC protection boxes.
Frequently asked questions
Do I need surge protection if my inverter has it built in?
External DC and AC SPDs are still recommended, especially in storm-prone areas: they take the hit and are inexpensive to replace.
Should I switch the system off during storms?
Not necessary with correct SPDs and earthing. Never work on the system during a storm.